120
120° circular (S)
Symmetric
Clear
Measured, RAN2-30-757-15 (taken as RAN2-30-757-120, to confirm)
Hazardous Area · High Bay and Low Bay
ATEX Low Bays & Pendant Lights
Order code RAN2-30-757-120-V1-UB-OR-I1
3,960 lm
CRI>70, 5700K. 120° circular (S) optic. OR Orange (RAL2011) - C5 rated.
No lumen is published for that combination.
30W nominal. 311 × 284 × 190 mm, 5.3 kg. CE, RoHS, ATEX, IECEx.
The Rankine Series is a mid-power, high-efficacy range of hazardous area low bay lights.
ATEX and IECEx certified, they are suitable for Zones 1/2 (gas) and 21/22 (dust). Featuring efficient light sources, marine-grade aluminium housings, and IP66 protection, they ensure long-term performance in harsh environments.
Each unit comes with an ATEX-certified cable gland and stopping plug, with inlet threads machined to specification. Quick installation is supported by multiple mounting options and a wire-in, wire-out terminal block - removing the need for extra junction boxes.
Designed for safety, reliability, and efficiency, they provide excellent visibility with minimal maintenance and energy use.
| Series code | RAN2 |
|---|---|
| Nominal power | 30W to 60W |
| Efficacy | 132lm/W to 139lm/W @ CRI>70, 5700K CCT |
| Lumen output | 3,960lm to 7,920lm |
| Lumen maintenance | L80B10 ≥50,000 hours @ 25°C ambient (TM21 reported), ≥76,685 hours (TM21 calculated) |
| Certification | CE, RoHS, ATEX, IECEx |
| Warranty | 5 Years |
Sheet lumen at CRI>70, 5700K, with no modification: 30 3,960 lm, 60 7,920 lm. Another CRI, or a modification, still prints the order code and leaves the lumen blank. 2 measured files give 132.2 to 134.2 lm/W; the measured figure for the chosen optic shows under the code.
Questions for Adam list what the sheet and the measured files do not settle yet.
120° circular (S)
Symmetric
Clear
Measured, RAN2-30-757-15 (taken as RAN2-30-757-120, to confirm)
Polar: solid green C0–C180, dashed blue C90–C270, dotted amber the plane through the brightest direction when it lies between them; rings at 25% steps of the peak. Isolux: the footprint on the floor with the fitting aimed straight down, contours at 50%, 25% and 10% of the brightest point, grid in mounting heights (H). Both are drawn from the first measured file for that optic.
Impact Resistance: Engineered for durability, the Rankine Series features a shock-and vibration-resistant tempered glass lens and a copper-free aluminium alloy housing. Designed to withstand impacts of up to 20 joules (IK10), it significantly reduces the risk of early failure in hazardous environments. Optional wire-guard protection can raise the glass diffuser's rating from IK08 to IK10. High Lumen Efficacy & Long Life: Delivering up to 139 lm/W at CRI>70 and 5700K, the Rankine Series combines high-output performance with energy efficiency. With a projected lumen maintenance of L70 at 120,000 hours, it ensures long-term reliability with minimal maintenance. Flexible Mounting Options: Designed for fast, adaptable installation, the Rankine Series supports multiple mounting methods including eye bolt, universal bracket, surface mount, and pipe clamp. Each unit is supplied with an inlet thread machined to specification, ensuring compatibility with on-site requirements and reducing setup time. Industrial Build Quality: Rated for operation in temperatures from -40°C to +55°C, and protected to IP66, the Rankine Series is built to perform in extreme conditions. Its corrosion-resistant construction makes it an ideal choice for offshore, petrochemical, and industrial environments. Safe and Streamlined Wiring: The terminal compartment is isolated from the LED light source, providing easy access during installation and maintenance. Wire-in, wire-out capability removes the need for additional junction boxes, reducing complexity and cost.


These lights provide sufficient coverage for vehicle loading and unloading of Hazardous Substances while providing resistance against hazardous conditions.

Lighting for Distilleries must find a balance between style and function; lights must offer optimum performance in vapour-filled environments.

Oil rig lights need to perform in harsh environments where safety is paramount. We offer a variety of LED ATEX explosion-proof lighting for oil rigs.

For oil refinery lighting and for the petro-chemical sector, Kellwood Lighting offer a range of marine grade LED ATEX / IECEx approved lighting products.

Lighting for grain processing and storage rooms must work in the presence of flammable dust, meeting regulations for hazardous areas and food production.
Showing 1-1 of 1
| Chip Brand, Model, & Size | Osram Duris S5 |
|---|---|
| Chip Efficacy @ CRI>70, 5000K CCT | 151lm/W |
| Light Emission | Direct |
| CCT | 5700K, (3000K, 4000K, 5000K optional) |
| CRI | ≥70, ≥80 |
| Diffusers | Clear |
| Symmetric Light Distribution | 120° |
| System Operating Power | RAN2-30: 30W; RAN2-60: 60W |
|---|---|
| Input Voltage | 100-240VAC |
| Input Frequency | 50-60Hz |
| Inrush Current @ 100-240VAC | 30A |
| Power Factor | >0.98 |
| THD | <10% (100VAC-240VAC) |
| Insulation Class | I |
| Surge Protection/Fusing | 5kV |
| IP Rating | IP66 |
|---|---|
| IK Rating | IK10 housing / IK08 front face, or IK10 / IK10 with the wire guard |
| Ambient Usage Tolerance | -40°C to 55°C |
| Marine Resistance Rating | C5 |
| Ambient Storage Tolerance | -40°C to 55°C |
| Ambient Humidity Tolerance | 0% to 90% RH |
| Product Dimensions: LxWxH (mm) | 311 x 284 x 190 |
|---|---|
| Qty of LED Chips | RAN2-30: 84; RAN2-60: 140 |
| Electrical Connection | Recommended 1mm² to 4mm² |
| Wire-In-Wire-Out Installation | Yes |
| Inlet Thread | M20 (M20x1.5), M25 (M25x1.5), NPT3/4” |
| Gland Type | Brass with Nickel Plated Non-Armoured (Armoured optional) |
| Suitable Cable Size (ø) | M20 = 6.1-13.2mm, M25 = 9.5-15.9mm, NPT3/4” = 12.5-20.5mm |
| Fixture Weight | 5.3kg (excludes bracketry) |
| Fixture Primary Material(s) | ADC12 Aluminium Alloy (1.5-3.5% Copper) and 316 Stainless Steel Fixings |
| Fixture Finish | Epoxy Powder Coated |
| Lens(es) Materials | Tempered Glass |
| Protection Method | Flame Proof |
| Mounting Styles | Universal Bracket, Eye Bolt, Surface Mount Bracket, Pipe Clamp Mount |
|---|---|
| Miscellaneous Accessories | Wire Grill |
| Available Product Colours | Orange (RAL2011), Grey (RAL7040) |
| Division | ATEX Zone 1 & 21 and 2 & 22 |
|---|---|
| Product marking | II 2 G D, Ex d IIB T* or T* Gb, Ex t IIIC T* or T* Db IP66 |
| Temperature class, -40° to 40°C (Ta) | 60W: gas T6, dust T80°C; 30W: not listed |
| Temperature class, -40° to 55°C (Ta) | 30W: gas T6, dust T80°C; 60W: gas T5, dust T95°C |
| Certificate numbers | ATEX: LCIE 12 ATEX 3070 X; IECEx: IECEx CQM 12.0033X |
| 30 | 30W nominal. 311 × 284 × 190 mm, 5.3 kg. CE, RoHS, ATEX, IECEx. |
|---|---|
| 60 | 60W nominal. 311 × 284 × 190 mm, 5.3 kg. CE, RoHS, ATEX, IECEx. |
Details are for the standard non-dimming driver. Fixture weight excludes bracketry.
IK rating format is housing / front face; IK10 front face when fitted with the wire guard.
Wire-in-wire-out products are supplied with one non-armoured ATEX certified gland and one ATEX certified blanking plug. Armoured cable glands are an option; contact Kellwood.
The stated cable size applies to the standard gland; armoured cable may vary.
Hazardous area certified product modifications are typically limited to bracketry, to keep certification. Products are supplied with OEM nameplates, codes and documentation corresponding to the certification.
If more than one modification is required, separate each modification with a hyphen at the end of the product code.
Modifications which affect light output have separate photometric files identified with +(modification).
Alternative drivers may be available. Contact the office for further details.
If the product is customised, the code is altered.
Contact the office for further information on driver parameters.
The Best Place to Install LED Drivers in Outdoor Sports Lighting ProjectsSports Lighting · Michael Boyom · 28th April, 2026
Should You Choose an ISO9001 Lighting Supplier?Business News · Adam Maitland · 18th April, 2026
Red-White LED Lighting for FETF 300 GrantsIndustrial Lighting · Adam Maitland · 24th March, 2026Our lights are used by
I am delighted to have used Kellwood...
P. Nisbet, Wabtec Corporationa project that was well planned and promptly accomplished
E. McHugh, LoganairWhere others let us down, Kellwood did not
W. Coley, Barking Abbey School...my client is over the moon with the end results
A. Fraser, MacLean ElectricalI'd certainly recommend them
V. Richardson, Stolle EuropeI'm more than pleased with the guys. I'd recommend them to anyone
G. Gray, Logoplaste